PUH Roof Units
|
 |
Features
|
| |
- The range covers sizes 355 - 630mm diameter horizontal roof units.
Construction
|
|
|
Impellers
|
|
|
Motors
|
- The following standard specifications apply:
- Totally enclosed IP55 or ECM motors as required. - 220-240V-1 PH-50Hz or 380-415V-3PH-50Hz - Protection on motor class can be specified. Standard motors with typically have IP55 class protection.
|
Soaker sheets
|
| |
- Soaker sheets are available in most modern roof profiles complete with integral up stands.
Selection procedure
|
| |
- The units are selected of the standard AMS Powerline Ultra Series curves allowing a K factor of 1.2.
Dimensions
|
|
 |
| |
| PUH |
A |
B |
C |
D |
E |
| 315 |
690 |
395 |
660 |
80 |
400 |
| 350 |
690 |
395 |
660 |
80 |
400 |
| 400 |
760 |
445 |
760 |
80 |
500 |
| 450 |
760 |
445 |
760 |
80 |
500 |
| 500 |
900 |
585 |
910 |
100 |
650 |
| 560 |
900 |
585 |
910 |
100 |
650 |
| 630 |
1020 |
670 |
1160 |
100 |
790 |
|
| |
Technical Data & Noise Levels
|
| PUH |
rev/sec |
Max Temp |
dB(A) @3m |
3ph kW |
Amps |
| 315 |
23 |
60 |
Inlet 46 |
0.37 |
1.07 |
| Outlet 50 |
| 350 |
23 |
60 |
Inlet 42 |
0.37 |
1.07 |
| Outlet 46 |
| 400 |
22 |
60 |
Inlet 49 |
0.75 |
2.15 |
| Outlet 52 |
| 450 |
23 |
60 |
Inlet 51 |
1.1 |
2.74 |
| Outlet 55 |
| 500 |
21 |
60 |
Inlet 56 |
1.5 |
3.66 |
| Outlet 60 |
| 560 |
22 |
45 |
Inlet 56 |
3.0 |
6.4 |
| Outlet 63 |
| 630 |
24 |
45 |
Inlet 61 |
5.5 |
10.5 |
| Outlet 66 |
|
|
| |